柱子承载力
最近建立了一根柱子的模型,可是通过ANSYS计算出来的承载力比手算出来的承载力要大25%左右,设置的混凝土强度的柱子尺寸都没有问题,不明白是什么地方出问题了,希望高手可以指教一下,谢谢! 有没有人指点么?比较急 详细说下你的计算过程 我在建模的时候选用的C30的混凝土,由于考虑到箍筋对混凝土的约束作用,所以应用了Mander的本构模型,计算它的英里应变曲线候设置混凝土特性,顺便说下柱子尺寸0.36×0.36,每边布置4根25的钢筋,箍筋是12的,间距10CM。tb,kinh,1,1,15 !确定混凝土的随动强化模型
tbpt,,0.0006,11.60e6 !确定混凝土的应力应变曲线
tbpt,,0.0009,15.58e6
tbpt,,0.0012,18.46e6
tbpt,,0.0018,21.80e6
tbpt,,0.0024,23.18e6
tbpt,,0.0030,23.50e6
tbpt,,0.0036,23.30e6
tbpt,,0.0042,22.83e6
tbpt,,0.0048,22.25e6
tbpt,,0.0054,21.63e6
tbpt,,0.0060,20.99e6
tbpt,,0.0066,20.37e6
tbpt,,0.0072,19.78e6
tbpt,,0.0078,19.22e6
tbpt,,0.0084,18.69e6
关系如上,利用它计算出来的混凝土的极限承载力是6230KN,可是利用手算出来的大概是5020KN,手算的时候利用的混凝土的强度也是23.5MP
希望能给指点一下,谢谢水兄!
[ 本帖最后由 yuntian 于 2007-5-18 08:48 编辑 ] 遇到过这样的问题,高手帮忙解释一下